UL 486F:2014 free download

admin
UL 486F:2014 free download

UL 486F:2014 free download Bare and Covered Ferrules
1 Scope
1.1 These requirements cover bare and covered ferrules intended for field wiring and factory wiring foruse in accordance with the National Electrical Code, ANSINFPA-70 and Canadian Electrical Code, cSAC22.1.
1.2 These ferrules are intended to facilitate the connection of stranded wire on to devices, such asterminal blocks.Their purpose is to treat stripped wire and prevent turned back strands during installation.They are intended to be used to attach to one stranded copper conductor or two stranded copperconductors of the same size.
1.3 These ferrules are suitable for use with 1/0 – 20 AWG stranded copper conductors.
1.4 These ferrules are intended to be terminated in wire connection devices rated for solid conductors.
1.5 Ferrules are not intended for use in IDC (insulation displacement connection) terminal blocks.
1.6 This standard does not apply to wire connectors such as pin adapters covered in CSA C22.2 No.65or UL 486A-486B.
2Reference Publications2.1 Normative references
Where reference is made to any Standards, such reference shall be considered to refer to the latesteditions and revisions thereto available at the time of printing, unless otherwise specified.
2.1.1 CSA Standards
C22.1-12
Canadian Electrical Code,Part l(CEC)
CAN/CSA-C22.2 No.0.17-O0(R2009)
Evaluation of Properties of Polymeric Materials
2.1.2 UL Standards
UL 94
Tests for Flammability of Plastic Materials for Parts in Devices and Appliances
UL 746C
Polymeric Materials – Use in Electrical Equipment Evaluations
2.1.3 NFPA* Standard
ANSI/NFPA 70-2011,
National Electrical Code (NEc)
*National Fire Protection Association3 Units of Measurement
3.1 The values given in sl(metric) units shall be normative, except for AWG conductor sizes. Any othervalues given are for information only.
4 Definitions
For the purpose of this Standard, the following terms and definitions apply.
4.1 Covered – Encased within material of composition or thickness that is not recognized as electricalinsulation.
4.1A Covered ferrule – A ferrule provided with a plastic sleeve.
4.2 Ferrule – A conductive sleeve used to facilitate the termination of stranded wire in devices used toterminate solid conductors.
4.3Plastic sleeve – A non-conductive plastic material used for identification purposes. The term”covering” is also referred to in the Standard as a “plastic sleeve”.
5 Symbols and Abbreviations
5.1°- Degree
5.2 AwG – American Wire Gage/gauge5.3 c- Celsius
5.4 mm2 – Squared millimeters
5.5 v – Volts
6 Construction6.1 General
6.1.1 A ferrule shall be provided with one opening to accept one or two stranded type copper conductorsapplied with compression tooling.